NINGBO CRRCTIMES TRANSDUCER TECHNOLOGY CO.,LTD.
|
Payment Terms: | T/T |
Place of Origin: | Zhejiang, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Applications:
For the electronic measurement of currents: AC, DC IMPL.,etc.,with galvanic isolation between the primary (high power) and the secondary (electronic) circuits.
Main technical data:
1. Primary normal current IPN: 1000A r.m.s
2. Primary current, measuring range IP: 0~+/-1400A
3. Measuring range: RMmin RMmax
with ±15V @±1000A max: 0Ω 19Ω
@±1400A max: 0Ω 1Ω
4. Secondary nominal output: 200mA rms
5. Conversion ratio: 1:5000
6. Supply voltage(+/-5%):±15V
7. Current consumption: 25mA + Secondary output current
8. Isolation test: Between the primary circuit and the secondary circuit: 6kVrms/50Hz/1min
Accuracy – Dynamic performance data:
1. Accuracy @ IPN,+25℃:±1%×Im
2. Non-linearity: ≤±0.1%×Im
3.Offset current: ≤±0.25mA(@+25℃)
4.Thermal drift: ±0.75mA(-25℃~+70℃)
5. Response time @90% of IP max:≤1us
6. dI/dt accurately followed: > 50A/us
7. Frequency bandwidth (-1dB) :DC..100kHz
General data:
1. Operating temperature: -25ºC~+70ºC
2. Storage temperature: -40 oC ~+85 oC
3. Secondary coil resistance: ≤40Ω
4. Weight: 2.2kg
5. Standards: EN50155
Features:
1. Hall effect measuring principle
2. Galvanic isolation between primary and secondary circuit
3. Insulated plastic case made of PPO recognized according to UL 94-V0
Dimension:
Remark: NT1000-SI current transducer has noΦ40 copper bar through center hole
Connection: